| 17 | using namespace openstudio::model; |
| 18 | |
| 19 | TEST_F(ModelFixture, CoolingTowerVariableSpeed_constructor) { |
| 20 | ::testing::FLAGS_gtest_death_test_style = "threadsafe"; |
| 21 | |
| 22 | ASSERT_EXIT( |
| 23 | { |
| 24 | Model m; |
| 25 | CoolingTowerVariableSpeed coolingTowerVariableSpeed(m); |
| 26 | |
| 27 | exit(0); |
| 28 | }, |
| 29 | ::testing::ExitedWithCode(0), ""); |
| 30 | |
| 31 | Model m; |
| 32 | |
| 33 | CoolingTowerVariableSpeed coolingTowerVariableSpeed(m); |
| 34 | |
| 35 | ASSERT_TRUE(coolingTowerVariableSpeed.modelType()); |
| 36 | EXPECT_EQ("CoolToolsCrossFlow", coolingTowerVariableSpeed.modelType().get()); |
| 37 | |
| 38 | EXPECT_FALSE(coolingTowerVariableSpeed.modelCoefficient()); |
| 39 | |
| 40 | ASSERT_TRUE(coolingTowerVariableSpeed.designInletAirWetBulbTemperature()); |
| 41 | EXPECT_EQ(25.5556, coolingTowerVariableSpeed.designInletAirWetBulbTemperature().get()); |
| 42 | |
| 43 | ASSERT_TRUE(coolingTowerVariableSpeed.designApproachTemperature()); |
| 44 | EXPECT_EQ(3.8889, coolingTowerVariableSpeed.designApproachTemperature().get()); |
| 45 | |
| 46 | ASSERT_TRUE(coolingTowerVariableSpeed.designRangeTemperature()); |
| 47 | EXPECT_EQ(5.5556, coolingTowerVariableSpeed.designRangeTemperature().get()); |
| 48 | |
| 49 | EXPECT_FALSE(coolingTowerVariableSpeed.designWaterFlowRate()); |
| 50 | EXPECT_TRUE(coolingTowerVariableSpeed.isDesignWaterFlowRateAutosized()); |
| 51 | |
| 52 | EXPECT_FALSE(coolingTowerVariableSpeed.designAirFlowRate()); |
| 53 | EXPECT_TRUE(coolingTowerVariableSpeed.isDesignAirFlowRateAutosized()); |
| 54 | |
| 55 | EXPECT_FALSE(coolingTowerVariableSpeed.designFanPower()); |
| 56 | EXPECT_TRUE(coolingTowerVariableSpeed.isDesignFanPowerAutosized()); |
| 57 | |
| 58 | ASSERT_TRUE(coolingTowerVariableSpeed.minimumAirFlowRateRatio()); |
| 59 | EXPECT_EQ(0.2, coolingTowerVariableSpeed.minimumAirFlowRateRatio().get()); |
| 60 | |
| 61 | ASSERT_TRUE(coolingTowerVariableSpeed.fractionofTowerCapacityinFreeConvectionRegime()); |
| 62 | EXPECT_EQ(0.125, coolingTowerVariableSpeed.fractionofTowerCapacityinFreeConvectionRegime().get()); |
| 63 | |
| 64 | ASSERT_TRUE(coolingTowerVariableSpeed.basinHeaterCapacity()); |
| 65 | EXPECT_EQ(0.0, coolingTowerVariableSpeed.basinHeaterCapacity().get()); |
| 66 | |
| 67 | ASSERT_TRUE(coolingTowerVariableSpeed.basinHeaterSetpointTemperature()); |
| 68 | EXPECT_EQ(2.0, coolingTowerVariableSpeed.basinHeaterSetpointTemperature().get()); |
| 69 | |
| 70 | EXPECT_FALSE(coolingTowerVariableSpeed.basinHeaterOperatingSchedule()); |
| 71 | |
| 72 | EXPECT_EQ("SaturatedExit", coolingTowerVariableSpeed.evaporationLossMode()); |
| 73 | EXPECT_FALSE(coolingTowerVariableSpeed.isEvaporationLossModeDefaulted()); |
| 74 | |
| 75 | EXPECT_EQ(0.2, coolingTowerVariableSpeed.evaporationLossFactor()); |
| 76 | EXPECT_TRUE(coolingTowerVariableSpeed.isEvaporationLossFactorDefaulted()); |
nothing calls this directly